ECOVENT PLUS
Heat Recovery Units
Installation, Operation and Maintenance Manual
A
1-
IMPORTANT
This manual must be read in full before Installation,
Operation and Maintenance of the units supplied
Contents page
1 Introduction 1
2 Receipt of Goods/Handling 1
3 Installation 1
4 Set-up 3
5 Wiring 3
6 Maintenance 6
7 Warranty 7
8 Declaration of Conformity 8
1 Introduction
The Ecovent Plus series is a range of heat recovery units,
direct and belt driven, with duties up to 2m³/s. Suitable for
plant-room, ceiling void and external locations, each unit will
have been supplied with either no pre-wiring, pre-wired to an
external isolator or with fitted control panel as specified at
the time of order. The standard operating temperature of
these units is –20 to +35°C.
For further technical details regarding dimensions and
weights, contact VES on 08702 404340, quoting the sales
order (SO) number and the unit type as found on the unit
nameplate
or visit www.ves.co.uk.
2 Receipt of Goods/Handling
Immediately upon receipt of goods, check for possible
damage in transit paying particular attention to fan impellers,
motor, flexible connections, coil connections and unit casing.
Prior to installation please check to ensure smooth rotation
of the impeller after transit. Also check to ensure that any
ancillary items are included. These will normally be supplied
fitted or, in the case of small items, taped to the unit.
In the event of any damage having occurred or if any item is
found to be missing, it is essential to inform VES Andover
Ltd. within 7 working days of delivery quoting sales order
number and the unit type, as found on the unit nameplate.
After this period, we would be unable to accept any claim for
damaged or missing goods.
IMPORTANT
Handles, lids, housings and coil connections must not be
used as lifting points
When moving the unit, handle with care and in such a
manner as to avoid damaging the external finish as this may
reduce the ability to resist corrosion. Units are to be rigged
and lifted using spreaders, taking into account the weight of
the unit, and lifting gear should be arranged so as not to
bear on the casework.
For further details, refer to the unit outline drawing.
3 Installation
The entire system must be considered for safety purposes
and it is the responsibility of the installer to ensure that all of
the equipment is installed in compliance with the
manufacturer’s recommendations, with due regard to the
current HEALTH AND SAFETY AT WORK ACT and conforms
to all relevant statutory regulations.
Where a unit is installed so that a failure of components
could result in injury to personnel, precautions should be
taken to prevent such an injury. If the unit is installed where
there is a reasonable possibility of persons or objects
coming into contact with the impeller, a guard should be
fitted.
It is the installer’s responsibility to ensure that access panels
are not obstructed in any way and safe working access for
maintenance must be provided in line with Health and Safety
and Building Regulations.
For optimum unit performance, careful consideration must be
paid to the location of the unit in relation to the ductwork and
associated items; placing the unit directly adjacent to a bend
in ductwork will impede airflow and reduce performance.
Consideration must also be given by the installer for
adequate illumination of the unit location in order for safe
maintenance.
Sectional (tubular framed) units should be assembled using
self-adhesive rubber tape at the joints prior to assembly so
as to prevent air leakage; replace with similar if damaged.
IMPORTANT
Only experienced fitters should undertake this work. Take
necessary safety precautions when working in elevated positions
Electric Heater Batteries
Supply to the heater should be 1ph or 3ph with separate
neutrals; confirmation of this can be found on the unit
nameplate. Cables should be of silicone rubber, fibreglass or
of a similar high temperature insulated type and be installed
to current I.E.E. Regulations, ensuring a sufficient earth
connection to the terminal provided. Care should be taken
not to overstrain the terminal pillars as this may permanently
damage the elements.
The heater is fitted with a manual reset high temperature cut-
out with normally closed (NC) terminals. The cut-out is set to
break if the duct temperature rises above 130°C and must be
connected in series with the main contactor coil circuit if the
heater is to be isolated in the event of overheating.
The electrical supply must be isolated before attempting to
reset the manual cut-out.
!
VES Ref: ID 618
Issue D
JULY 2006
!
!
Supply fan
Controls (optional)
Plate heat
exchanger
Filter (Extract)
Extract fan
Face & bypass
damper
LPHW Section
EHB Section
Filter (Supply)
Fig.1 Typical unit layout
Seitenansicht 0
1 2 3 4 5 6 7 8

Inhaltsverzeichnis

Seite 1 - Heat Recovery Units

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NFTel: 08702 404340 Fax: 08702 404550 E-mail: [email protected] Web: ww

Seite 2

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NFTel: 08702 404340 Fax: 08702 404550 E-mail: [email protected] Web: ww

Seite 3

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NFTel: 08702 404340 Fax: 08702 404550 E-mail: [email protected] Web: ww

Seite 4 - 5 Wiring continued

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NFTel: 08702 404340 Fax: 08702 404550 E-mail: [email protected] Web: ww

Seite 5

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NFTel: 08702 404340 Fax: 08702 404550 E-mail: [email protected] Web: ww

Seite 6 - Fax 08702 40 45 50

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NFTel: 08702 404340 Fax: 08702 404550 E-mail: [email protected] Web: ww

Seite 7

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NFTel: 08702 404340 Fax: 08702 404550 E-mail: [email protected] Web: ww

Seite 8 - Declaration of Conformity

VES Andover Ltd Eagle Close Chandlers Ford Ind. Est Eastleigh Hampshire SO53 4NFTel: 08702 404340 Fax: 08702 404550 E-mail: [email protected] Web: ww

Kommentare zu diesen Handbüchern

Keine Kommentare